Transformer
This article is about the electrical device .  For  the toy line franchise, see Transformers.   For other uses, see Transformer (disambiguation).
Pole-mounted power distribution transformer with center-tapped  secondary winding (note use of grounded conductor,  right, as one leg of the primary feeder). It transforms the high voltage  of the overhead distribution wires to the lower voltage used in house  wiring.
A transformer is a device that transfers electrical energy from one circuit to another through inductively coupled conductors—the transformer's coils. A  varying current in the first or primary  winding creates a varying magnetic  flux in the transformer's core and thus a varying magnetic field through the secondary winding. This  varying magnetic field induces a varying electromotive force (EMF) or "voltage" in  the secondary winding. This effect is called mutual induction.
If a load is connected to the secondary, an  electric current will flow in the secondary winding and electrical  energy will be transferred from the primary circuit through the  transformer to the load. In an ideal transformer, the induced voltage in  the secondary winding (Vs) is in proportion to the  primary voltage (Vp), and is given by the ratio of the  number of turns in the secondary (Ns) to the number  of turns in the primary (Np) as follows:
By appropriate selection of the ratio of turns, a transformer thus  allows an alternating current (AC) voltage to be  "stepped up" by making Ns greater than Np,  or "stepped down" by making Ns less than Np.
In the vast majority of transformers, the windings are coils wound  around a ferromagnetic core, air-core transformers being a notable exception.
Transformers range in size from a thumbnail-sized coupling  transformer hidden inside a stage microphone  to huge units weighing hundreds of tons used to interconnect portions  of power grids. All operate with the same basic  principles, although the range of designs is wide. While new  technologies have eliminated the need for transformers in some  electronic circuits, transformers are still found in nearly all  electronic devices designed for household ("mains") voltage. Transformers are essential  for high-voltage electric power transmission,  which makes long-distance transmission economically practical.
History
Discovery
The phenomenon of electromagnetic induction was  discovered independently by Michael Faraday and Joseph  Henry in 1831. However, Faraday was the first to publish the  results of his experiments and thus receive credit for the discovery.[2]  The relationship between electromotive force (EMF) or "voltage" and magnetic  flux was formalized in an equation now  referred to as "Faraday's law of induction":
.
where 
  is the magnitude of the EMF in volts and ΦB is the magnetic  flux through the circuit (in webers).[3]
  is the magnitude of the EMF in volts and ΦB is the magnetic  flux through the circuit (in webers).[3]Faraday performed the first experiments on induction between coils of  wire, including winding a pair of coils around an iron ring, thus  creating the first toroidal closed-core transformer.[4]
Induction coils
The first type of transformer to see wide use was the induction coil, invented by Rev. Nicholas Callan of Maynooth College, Ireland in 1836. He  was one of the first researchers to realize that the more turns the  secondary winding has in relation to the primary winding, the larger is  the increase in EMF. Induction coils evolved from scientists' and  inventors' efforts to get higher voltages from batteries. Since  batteries produce direct current (DC) rather than alternating current (AC),  induction coils relied upon vibrating electrical contacts that regularly  interrupted the current in the primary to create the flux changes  necessary for induction. Between the 1830s and the 1870s, efforts to  build better induction coils, mostly by trial and error, slowly revealed  the basic principles of transformers.
By the 1870s, efficient generators  that produced alternating current (alternators)  were available, and it was found that alternating current could power  an induction coil directly, without an interrupter. In 1876, Russian  engineer Pavel Yablochkov invented a lighting system  based on a set of induction coils where the primary windings were  connected to a source of alternating current and the secondary windings  could be connected to several "electric candles" (arc lamps) of his own design.[5][6]  The coils Yablochkov employed functioned essentially as transformers.[5]
In 1878, the Ganz  Company in Hungary began manufacturing equipment for electric  lighting and, by 1883, had installed over fifty systems in Austria-Hungary. Their systems used  alternating current exclusively and included those comprising both arc and incandescent lamps,  along with generators and  other equipment.[7]
Lucien Gaulard and John Dixon  Gibbs first exhibited a device with an open iron core called a  "secondary generator" in London in 1882, then sold the idea to the Westinghouse  company in the United States.[8]  They also exhibited the invention in Turin, Italy  in 1884, where it was adopted for an electric lighting system.[9]  However, the efficiency of their open-core bipolar apparatus remained  very low.[10]
Induction coils with open magnetic circuits are inefficient for  transfer of power to loads. Until about 1880, the paradigm for AC power  transmission from a high voltage supply to a low voltage load was a series circuit. Open-core transformers with a ratio  near 1:1 were connected with their primaries in series to allow use of a  high voltage for transmission while presenting a low voltage to the  lamps. The inherent flaw in this method was that turning off a single  lamp affected the voltage supplied to all others on the same circuit.  Many adjustable transformer designs were introduced to compensate for  this problematic characteristic of the series circuit, including those  employing methods of adjusting the core or bypassing the magnetic flux  around part of a coil.[11]
Efficient, practical transformer designs did not appear until the  1880s, but within a decade the transformer would be instrumental in the "War of Currents", and in seeing AC distribution systems  triumph over their DC counterparts, a position in which they have  remained dominant ever since.
The transformer is based on two principles: first, that an electric current can produce a magnetic field (electromagnetism), and, second that a  changing magnetic field within a coil of wire induces a voltage across  the ends of the coil (electromagnetic induction).  Changing the current in the primary coil changes the magnetic flux that  is developed. The changing magnetic flux induces a voltage in the  secondary coil.
An ideal transformer is shown in the adjacent figure. Current passing  through the primary coil creates a magnetic field. The primary and secondary coils are wrapped  around a core of very high magnetic permeability, such  as iron, so  that most of the magnetic flux passes through both the primary and  secondary coils.
Induction law
The voltage induced across the secondary coil may be calculated from Faraday's law of induction, which  states that:

where Vs is the instantaneous voltage,  Ns is the number of turns in the secondary coil and Φ  is the magnetic flux through one turn of the coil. If  the turns of the coil are oriented perpendicular to the magnetic field  lines, the flux is the product of the magnetic flux density  B and the area A through which it cuts. The area is  constant, being equal to the cross-sectional area of the transformer  core, whereas the magnetic field varies with time according to the  excitation of the primary. Since the same magnetic flux passes through  both the primary and secondary coils in an ideal transformer,[29]  the instantaneous voltage across the primary winding equals
Taking the ratio of the two equations for Vs and Vp  gives the basic equation[30]  for stepping up or stepping down the voltage
Np/Ns is known as the turns  ratio, and is the primary functional characteristic of any  transformer. In the case of step-up transformers, this may sometimes be  stated as the reciprocal, Ns/Np. Turns  ratio is commonly expressed as an irreducible fraction or ratio: for  example, a transformer with primary and secondary windings of,  respectively, 100 and 150 turns is said to have a turns ratio of 2:3  rather than 0.667 or 100:150.
Ideal power equation
If the secondary coil is attached to a load that allows current to  flow, electrical power is transmitted from the primary circuit to the  secondary circuit. Ideally, the transformer is perfectly efficient; all  the incoming energy is transformed from the primary circuit to the magnetic field and into the secondary circuit. If this  condition is met, the incoming electric power must equal the outgoing power:
giving the ideal transformer equation
Transformers normally have high efficiency, so this formula is a  reasonable approximation.
If the voltage is increased, then the current is decreased by the  same factor. The impedance in one circuit is transformed by the square  of the turns ratio.[29]  For example, if an impedance Zs is attached across  the terminals of the secondary coil, it appears to the primary circuit  to have an impedance of (Np/Ns)2Zs.  This relationship is reciprocal, so that the impedance Zp  of the primary circuit appears to the secondary to be (Ns/Np)2Zp.
Detailed operation
The simplified description above neglects several practical factors,  in particular the primary current required to establish a magnetic field  in the core, and the contribution to the field due to current in the  secondary circuit.
Models of an ideal transformer typically assume a core of negligible reluctance with two windings of zero resistance.[31]  When a voltage is applied to the primary winding, a small current  flows, driving flux around the magnetic circuit of the core.[31]  The current required to create the flux is termed the magnetizing  current; since the ideal core has been assumed to have near-zero  reluctance, the magnetizing current is negligible, although still  required to create the magnetic field.
The changing magnetic field induces an electromotive force (EMF) across each  winding.[32]  Since the ideal windings have no impedance, they have no associated  voltage drop, and so the voltages VP and VS  measured at the terminals of the transformer, are equal to the  corresponding EMFs. The primary EMF, acting as it does in opposition to  the primary voltage, is sometimes termed the "back EMF".[33]  This is due to Lenz's law which states that the induction of EMF  would always be such that it will oppose development of any such change  in magnetic field.
Leakage flux
Main article: Leakage inductance
The ideal transformer model assumes that all flux generated by the  primary winding links all the turns of every winding, including itself.  In practice, some flux traverses paths that take it outside the  windings.[34]  Such flux is termed leakage flux, and results in leakage inductance in series with the mutually  coupled transformer windings.[33]  Leakage results in energy being alternately stored in and discharged  from the magnetic fields with each cycle of the power  supply. It is not directly a power loss (see "Stray losses"  below), but results in inferior voltage regulation, causing the secondary voltage to  fail to be directly proportional to the primary, particularly under  heavy load.[34]  Transformers are therefore normally designed to have very low leakage inductance.
However, in some applications, leakage can be a desirable property,  and long magnetic paths, air gaps, or magnetic bypass shunts may be  deliberately introduced to a transformer's design to limit the short-circuit current it will supply.[33]  Leaky transformers may be used to supply loads that exhibit negative resistance, such as electric  arcs, mercury vapor lamps,  and neon  signs; or for safely handling loads that become periodically  short-circuited such as electric  arc welders.[35]
Air gaps are also used to keep a transformer from saturating,  especially audio-frequency transformers in circuits that have a direct  current flowing through the windings.[citation needed]
Leakage inductance is also helpful when transformers are operated in  parallel. It can be shown that if the "per-unit" inductance of two  transformers is the same (a typical value is 5%), they will  automatically split power "correctly" (e.g. 500 kVA unit in parallel  with 1,000 kVA unit, the larger one will carry twice the current).[citation needed]
Effect of frequency
 Transformer  universal EMF equation
If the flux in the core is purely sinusoidal, the relationship for either winding between its rms voltage Erms of the winding , and the supply frequency f, number of turns N, core cross-sectional area a and peak magnetic flux density B is given by the universal EMF equation:[31]

If the flux does not contain even harmonics the following equation can be used for half-cycle average voltage Eavg of any waveshape:

If the flux in the core is purely sinusoidal, the relationship for either winding between its rms voltage Erms of the winding , and the supply frequency f, number of turns N, core cross-sectional area a and peak magnetic flux density B is given by the universal EMF equation:[31]

If the flux does not contain even harmonics the following equation can be used for half-cycle average voltage Eavg of any waveshape:

The time-derivative term in Faraday's Law shows that the flux  in the core is the integral with respect to time of the applied  voltage.[36]  Hypothetically an ideal transformer would work with direct-current  excitation, with the core flux increasing linearly with time.[37]  In practice, the flux would rise to the point where magnetic saturation of the core  occurs, causing a huge increase in the magnetizing current and  overheating the transformer. All practical transformers must therefore  operate with alternating (or pulsed) current.[37]
The EMF of a transformer at a given flux density increases with  frequency.[31]  By operating at higher frequencies, transformers can be physically more  compact because a given core is able to transfer more power without  reaching saturation and fewer turns are needed to achieve the same  impedance. However, properties such as core loss and conductor skin  effect also increase with frequency. Aircraft and military  equipment employ 400 Hz power supplies which reduce core and winding  weight.[38]  Conversely, frequencies used for some railway electrification systems  were much lower (e.g. 16.7 Hz and 25 Hz) than normal utility  frequencies (50 – 60 Hz) for historical reasons concerned mainly with  the limitations of early electric traction motors. As such, the transformers used to  step down the high over-head line voltages (e.g. 15 kV) are much heavier  for the same power rating than those designed only for the higher  frequencies.
Operation of a transformer at its designed voltage but at a higher  frequency than intended will lead to reduced magnetizing current; at  lower frequency, the magnetizing current will increase. Operation of a  transformer at other than its design frequency may require assessment of  voltages, losses, and cooling to establish if safe operation is  practical. For example, transformers may need to be equipped with "volts  per hertz" over-excitation relays to protect the transformer from overvoltage at higher  than rated frequency.
One example of state-of-the-art design is those transformers used for  electric multiple unit high speed trains, particularly those required to operate  across the borders of countries using different standards of  electrification. The position of such transformers is restricted to  being hung below the passenger compartment. They have to function at  different frequencies (down to 16.7 Hz) and voltages (up to 25 kV)  whilst handling the enhanced power requirements needed for operating the  trains at high speed.
Knowledge of natural frequencies of transformer windings is of  importance for the determination of the transient response of the  windings to impulse and switching surge voltages.
Energy losses
An ideal transformer would have no energy losses, and would be 100%  efficient. In practical transformers energy is dissipated in the  windings, core, and surrounding structures. Larger transformers are  generally more efficient, and those rated for electricity distribution  usually perform better than 98%.[39]
Experimental transformers using superconducting windings achieve  efficiencies of 99.85%.[40]  The increase in efficiency can save considerable energy, and hence  money, in a large heavily-loaded transformer; the trade-off is in the  additional initial and running cost of the superconducting design.
Losses in transformers (excluding associated circuitry) vary with  load current, and may be expressed as "no-load" or "full-load" loss.  Winding resistance  dominates load losses, whereas hysteresis  and eddy currents losses contribute to over 99% of the no-load  loss. The no-load loss can be significant, so that even an idle  transformer constitutes a drain on the electrical supply and a running  cost; designing transformers for lower loss requires a larger core,  good-quality silicon steel, or even amorphous steel, for the core, and thicker  wire, increasing initial cost, so that there is a trade-off  between initial cost and running cost. (Also see energy efficient transformer).[41]
Transformer losses are divided into losses in the windings, termed copper  loss, and those in the magnetic circuit, termed iron loss. Losses in the transformer arise from:
- Winding resistance
 - Current flowing through the windings causes resistive heating of the conductors. At higher frequencies, skin effect and proximity effect create additional winding resistance and losses.
 - Hysteresis losses
 - Each time the magnetic field is reversed, a small amount of energy is lost due to hysteresis within the core. For a given core material, the loss is proportional to the frequency, and is a function of the peak flux density to which it is subjected.[41]
 - Eddy currents
 - Ferromagnetic materials are also good conductors, and a core made from such a material also constitutes a single short-circuited turn throughout its entire length. Eddy currents therefore circulate within the core in a plane normal to the flux, and are responsible for resistive heating of the core material. The eddy current loss is a complex function of the square of supply frequency and inverse square of the material thickness.[41] Eddy current losses can be reduced by making the core of a stack of plates electrically insulated from each other, rather than a solid block; all transformers operating at low frequencies use laminated or similar cores.
 - Magnetostriction
 - Magnetic flux in a ferromagnetic material, such as the core, causes it to physically expand and contract slightly with each cycle of the magnetic field, an effect known as magnetostriction. This produces the buzzing sound commonly associated with transformers,[30] and can cause losses due to frictional heating.
 - Mechanical losses
 - In addition to magnetostriction, the alternating magnetic field causes fluctuating forces between the primary and secondary windings. These incite vibrations within nearby metalwork, adding to the buzzing noise, and consuming a small amount of power.[42]
 - Stray losses
 - Leakage inductance is by itself largely lossless, since energy supplied to its magnetic fields is returned to the supply with the next half-cycle. However, any leakage flux that intercepts nearby conductive materials such as the transformer's support structure will give rise to eddy currents and be converted to heat.[43] There are also radiative losses due to the oscillating magnetic field, but these are usually small.
 
Dot convention
Main article: Dot convention
It is common in transformer schematic symbols for there to be a dot  at the end of each coil within a transformer, particularly for  transformers with multiple primary and secondary windings. The dots  indicate the direction of each winding relative to the others. Voltages  at the dot end of each winding are in phase; current flowing into the  dot end of a primary coil will result in current flowing out of the dot  end of a secondary coil.
Equivalent circuit
- Refer to the diagram below
 
The physical limitations of the practical transformer may be brought  together as an equivalent circuit model (shown below) built around an  ideal lossless transformer.[44]  Power loss in the windings is current-dependent and is represented as  in-series resistances Rp and Rs.  Flux leakage results in a fraction of the applied voltage dropped  without contributing to the mutual coupling, and thus can be modeled as  reactances of each leakage inductance Xp and Xs  in series with the perfectly coupled region.
Iron losses are caused mostly by hysteresis and eddy current effects  in the core, and are proportional to the square of the core flux for  operation at a given frequency.[45]  Since the core flux is proportional to the applied voltage, the iron  loss can be represented by a resistance RC in parallel  with the ideal transformer.
A core with finite permeability requires a  magnetizing current Im to maintain the mutual flux in  the core. The magnetizing current is in phase with the flux; saturation  effects cause the relationship between the two to be non-linear, but for  simplicity this effect tends to be ignored in most circuit equivalents.[45]  With a sinusoidal supply, the core  flux lags the induced EMF by 90° and this effect can be modeled as a  magnetizing reactance (reactance of an effective inductance) Xm  in parallel with the core loss  component. Rc and Xm are sometimes  together termed the magnetizing branch of the model. If the  secondary winding is made open-circuit, the current I0  taken by the magnetizing branch represents the transformer's no-load  current.[44]
The secondary impedance Rs and Xs  is frequently moved (or "referred") to the primary side after  multiplying the components by the impedance scaling factor (Np/Ns)2.
The resulting model is sometimes termed the "exact equivalent  circuit", though it retains a number of approximations, such as an  assumption of linearity.[44]  Analysis may be simplified by moving the magnetizing branch to the left  of the primary impedance, an implicit assumption that the magnetizing  current is low, and then summing primary and referred secondary  impedances, resulting in so-called equivalent impedance.
The parameters of equivalent circuit of a transformer can be  calculated from the results of two transformer tests: open-circuit test and short-circuit test.
Autotransformer
Main article: Autotransformer
In an autotransformer portions of the same winding act as both the primary and secondary. The winding has at least  three taps where electrical connections are  made. An autotransformer can be smaller, lighter and cheaper than a  standard dual-winding transformer however the autotransformer does not  provide electrical isolation.
Autotransformers are often used to step up or down between voltages  in the 110-117-120 volt range and voltages in the 220-230-240 volt  range, e.g., to output either 110 or 120V (with taps) from 230V input,  allowing equipment from a 100 or 120V region to be used in a 230V  region.
A variable autotransformer is made by exposing part of the winding  coils and making the secondary connection through a sliding brush, giving a variable turns ratio.[46]  Such a device is often referred to by the trademark name variac.
Polyphase transformers
For more details on this topic,  see Three-phase electric power.
For three-phase supplies, a bank of three individual  single-phase transformers can be used, or all three phases can be  incorporated as a single three-phase transformer. In this case, the  magnetic circuits are connected together, the core thus containing a  three-phase flow of flux.[47]  A number of winding configurations are possible, giving rise to  different attributes and phase shifts.[48]  One particular polyphase configuration is the zigzag transformer, used for grounding and in the suppression of harmonic  currents.[49]
Leakage transformers
A leakage transformer, also called a stray-field transformer, has a  significantly higher leakage inductance than other transformers, sometimes  increased by a magnetic bypass or shunt in its core between primary and  secondary, which is sometimes adjustable with a set screw. This provides  a transformer with an inherent current limitation due to the loose  coupling between its primary and the secondary windings. The output and  input currents are low enough to prevent thermal overload under all load  conditions—even if the secondary is shorted.
Leakage transformers are used for arc  welding and high voltage discharge lamps (neon lights and cold cathode  fluorescent lamps, which are series-connected up to 7.5 kV AC). It  acts then both as a voltage transformer and as a magnetic ballast.
Other applications are short-circuit-proof extra-low voltage transformers for toys or doorbell  installations.
Resonant transformers
For more details on this topic,  see Resonant inductive coupling.
A resonant transformer is a kind of  leakage transformer. It uses the leakage inductance of its secondary windings in  combination with external capacitors, to create one or more resonant circuits. Resonant  transformers such as the Tesla  coil can generate very high voltages, and are able to provide much  higher current than electrostatic high-voltage generation machines such  as the Van de Graaff generator.[50]  One of the applications of the resonant transformer is for the CCFL  inverter. Another application of the resonant transformer is to  couple between stages of a superheterodyne receiver, where the  selectivity of the receiver is provided by tuned transformers in the  intermediate-frequency amplifiers.[51]
Audio transformers
Audio transformers are those specifically designed for use in audio  circuits. They can be used to block radio frequency interference or the  DC component of an audio signal, to split or combine audio signals, or  to provide impedance matching between high and low impedance circuits,  such as between a high impedance tube (valve) amplifier output and a low impedance loudspeaker,  or between a high impedance instrument output and the low impedance  input of a mixing console.
Such transformers were originally designed to connect different  telephone systems to one another while keeping their respective power  supplies isolated, and are still commonly used to interconnect professional audio systems or system  components.
Being magnetic devices, audio transformers are susceptible to  external magnetic fields such as those generated by AC current-carrying  conductors. "Hum" is a term commonly used to describe unwanted signals  originating from the "mains" power supply (typically 50 or 60 Hz). Audio  transformers used for low-level signals, such as those from microphones,  often include shielding to protect against extraneous magnetically  coupled signals.
Instrument transformers
Instrument transformers are used for measuring voltage and current in  electrical power systems, and for power system protection and control. Where a  voltage or current is too large to be conveniently used by an  instrument, it can be scaled down to a standardized, low value.  Instrument transformers isolate measurement, protection and control  circuitry from the high currents or voltages present on the circuits  being measured or controlled.
A current transformer is a transformer  designed to provide a current in its secondary coil proportional to the  current flowing in its primary coil.[52]
Voltage transformers (VTs), also referred  to as "potential transformers" (PTs), are designed to have an  accurately known transformation ratio in both magnitude and phase, over a  range of measuring circuit impedances. A voltage transformer is  intended to present a negligible load to the supply being measured. The  low secondary voltage allows protective relay equipment and measuring  instruments to be operated at a lower voltages.[53]
Both current and voltage instrument transformers are designed to have  predictable characteristics on overloads. Proper operation of  over-current protective relays requires that current  transformers provide a predictable transformation ratio even during a  short-circuit.
Classification
Transformers can be considered a class of electric machine with no moving parts; as such they are  described as static electric machines. They can be classified in  many different ways; an incomplete list is:
- By power capacity: from a fraction of a volt-ampere (VA) to over a thousand MVA;
 - By frequency range: power-, audio-, or radio frequency;
 - By voltage class: from a few volts to hundreds of kilovolts;
 - By cooling type: air-cooled, oil-filled, fan-cooled, or water-cooled;
 - By application: such as power supply, impedance matching, output voltage and current stabilizer, or circuit isolation;
 - By purpose: distribution, rectifier, arc furnace, amplifier output, etc.;
 - By winding turns ratio: step-up, step-down, isolating with equal or near-equal ratio, variable, multiple windings.
 
Construction
Cores
Transformers for use at power or audio frequencies typically have  cores made of high permeability silicon steel.[54]  The steel has a permeability many times that of free space, and the core thus serves to greatly  reduce the magnetizing current, and confine the flux to a path which  closely couples the windings.[55]  Early transformer developers soon realized that cores constructed from  solid iron resulted in prohibitive eddy-current losses, and their  designs mitigated this effect with cores consisting of bundles of  insulated iron wires.[8]  Later designs constructed the core by stacking layers of thin steel  laminations, a principle that has remained in use. Each lamination is  insulated from its neighbors by a thin non-conducting layer of  insulation.[47]  The universal transformer equation indicates a  minimum cross-sectional area for the core to avoid saturation.
The effect of laminations is to confine eddy currents to highly  elliptical paths that enclose little flux, and so reduce their  magnitude. Thinner laminations reduce losses,[54]  but are more laborious and expensive to construct.[56]  Thin laminations are generally used on high frequency transformers,  with some types of very thin steel laminations able to operate up to  10 kHz.
One common design of laminated core is made from interleaved stacks  of E-shaped steel sheets capped with I-shaped pieces, leading to its name of "E-I  transformer".[56]  Such a design tends to exhibit more losses, but is very economical to  manufacture. The cut-core or C-core type is made by winding a steel  strip around a rectangular form and then bonding the layers together. It  is then cut in two, forming two C shapes, and the core assembled by  binding the two C halves together with a steel strap.[56]  They have the advantage that the flux is always oriented parallel to  the metal grains, reducing reluctance.
A steel core's remanence means that it retains a static magnetic  field when power is removed. When power is then reapplied, the residual  field will cause a high inrush current until the effect of the remaining magnetism  is reduced, usually after a few cycles of the applied alternating  current.[57]  Overcurrent protection devices such as fuses must be selected to allow this harmless inrush  to pass. On transformers connected to long, overhead power transmission  lines, induced currents due to geomagnetic disturbances  during solar storms can cause saturation of the  core and operation of transformer protection devices.[58]
Distribution transformers can achieve low no-load losses by using  cores made with low-loss high-permeability silicon steel or amorphous (non-crystalline) metal  alloy. The higher initial cost of the core material is offset over  the life of the transformer by its lower losses at light load.[59]
Solid cores
Powdered iron  cores are used in circuits (such as switch-mode power supplies) that  operate above main frequencies and up to a few tens of kilohertz. These  materials combine high magnetic permeability with high bulk  electrical resistivity. For frequencies  extending beyond the VHF band, cores made from non-conductive magnetic ceramic  materials called ferrites are common.[56]  Some radio-frequency transformers also have movable cores (sometimes  called 'slugs') which allow adjustment of the coupling coefficient (and bandwidth) of tuned  radio-frequency circuits.
Toroidal cores
Toroidal transformers are built around a ring-shaped core, which,  depending on operating frequency, is made from a long strip of silicon steel or permalloy  wound into a coil, powdered iron, or ferrite.[60]  A strip construction ensures that the grain boundaries are optimally aligned, improving the  transformer's efficiency by reducing the core's reluctance. The closed ring shape eliminates air  gaps inherent in the construction of an E-I core.[35]  The cross-section of the ring is usually square or rectangular, but  more expensive cores with circular cross-sections are also available.  The primary and secondary coils are often wound concentrically to cover  the entire surface of the core. This minimizes the length of wire  needed, and also provides screening to minimize the core's magnetic  field from generating electromagnetic interference.
Toroidal transformers are more efficient than the cheaper laminated  E-I types for a similar power level. Other advantages compared to E-I  types, include smaller size (about half), lower weight (about half),  less mechanical hum (making them superior in audio amplifiers), lower  exterior magnetic field (about one tenth), low off-load losses (making  them more efficient in standby circuits), single-bolt mounting, and  greater choice of shapes. The main disadvantages are higher cost and  limited power capacity (see "Classification" above). Because of the lack  of a residual gap in the magnetic path, toroidal transformers also tend  to exhibit higher inrush current, compared to laminated E-I types.
Ferrite toroidal cores are used at higher frequencies, typically  between a few tens of kilohertz to hundreds of megahertz, to reduce  losses, physical size, and weight of switch-mode power supplies. A  drawback of toroidal transformer construction is the higher labor cost  of winding. This is because it is necessary to pass the entire length of  a coil winding through the core aperture each time a single turn is  added to the coil. As a consequence, toroidal transformers are uncommon  above ratings of a few kVA. Small distribution transformers may achieve  some of the benefits of a toroidal core by splitting it and forcing it  open, then inserting a bobbin containing primary and secondary windings.
Air cores
A physical core is not an absolute requisite and a functioning  transformer can be produced simply by placing the windings near each  other, an arrangement termed an "air-core" transformer. The air which  comprises the magnetic circuit is essentially lossless, and so an  air-core transformer eliminates loss due to hysteresis  in the core material.[33]  The leakage inductance is inevitably high, resulting in very poor  regulation, and so such designs are unsuitable for use in power  distribution.[33]  They have however very high bandwidth, and are frequently  employed in radio-frequency applications,[61]  for which a satisfactory coupling coefficient is maintained by  carefully overlapping the primary and secondary windings. They're also  used for resonant transformers  such as Tesla coils where they can achieve reasonably low loss in  spite of the high leakage inductance.
Windings
Cut view through transformer windings. White: insulator. Green spiral: Grain oriented silicon steel. Black: Primary winding made of oxygen-free copper. Red: Secondary  winding. Top left: Toroidal transformer. Right: C-core, but E-core would  be similar. The black windings are made of film. Top: Equally low  capacitance between all ends of both windings. Since most cores are at  least moderately conductive they also need insulation. Bottom: Lowest  capacitance for one end of the secondary winding needed for low-power  high-voltage transformers. Bottom left: Reduction of leakage inductance would lead to increase of  capacitance.
The conducting material used for the  windings depends upon the application, but in all cases the individual  turns must be electrically insulated from each other to ensure that the  current travels throughout every turn.[36]  For small power and signal transformers, in which currents are low and  the potential difference between adjacent turns is small, the coils are  often wound from enamelled magnet wire, such as Formvar wire.  Larger power transformers operating at high voltages may be wound with  copper rectangular strip conductors insulated by oil-impregnated paper  and blocks of pressboard.[62]
High-frequency transformers operating in the tens to hundreds of  kilohertz often have windings made of braided Litz  wire to minimize the skin-effect and proximity effect  losses.[36]  Large power transformers use multiple-stranded conductors as well,  since even at low power frequencies non-uniform distribution of current  would otherwise exist in high-current windings.[62]  Each strand is individually insulated, and the strands are arranged so  that at certain points in the winding, or throughout the whole winding,  each portion occupies different relative positions in the complete  conductor. The transposition equalizes the current flowing in each  strand of the conductor, and reduces eddy current losses in the winding  itself. The stranded conductor is also more flexible than a solid  conductor of similar size, aiding manufacture.[62]
For signal transformers, the windings may be arranged in a way to  minimize leakage inductance and stray capacitance to improve  high-frequency response. This can be done by splitting up each coil into  sections, and those sections placed in layers between the sections of  the other winding. This is known as a stacked type or interleaved  winding.
Both the primary and secondary windings on power transformers may  have external connections, called taps, to intermediate points on the winding to allow  selection of the voltage ratio. In distribution transformers the taps  may be connected to an automatic on-load tap changer for voltage regulation of  distribution circuits. Audio-frequency transformers, used for the  distribution of audio to public address loudspeakers, have taps to allow  adjustment of impedance to each speaker. A center-tapped  transformer is often used in the output stage of an audio power amplifier  in a push-pull circuit.  Modulation transformers in AM transmitters are very similar.
Certain transformers have the windings protected by epoxy resin. By impregnating the transformer with epoxy under a vacuum,  one can replace air spaces within the windings with epoxy, thus sealing  the windings and helping to prevent the possible formation of corona and  absorption of dirt or water. This produces transformers more suited to  damp or dirty environments, but at increased manufacturing cost.[63]
Coolant
High temperatures will damage the winding insulation.[64]  Small transformers do not generate significant heat and are  cooled by air circulation and radiation  of heat. Power transformers rated up to several hundred kVA can be  adequately cooled by natural convective  air-cooling, sometimes assisted by fans.[65]  In larger transformers, part of the design problem is removal of heat.  Some power transformers are immersed in transformer oil that both cools and insulates the windings.[66]  The oil is a highly refined mineral  oil that remains stable at transformer operating temperature. Indoor  liquid-filled transformers are required by building regulations in many  jurisdictions to use a non-flammable liquid, or to be located in  fire-resistant rooms.[67]  Air-cooled dry transformers are preferred for indoor applications even  at capacity ratings where oil-cooled construction would be more  economical, because their cost is offset by the reduced building  construction cost.
The oil-filled tank often has radiators through which the oil  circulates by natural convection; some large transformers employ forced  circulation of the oil by electric pumps, aided by external fans or  water-cooled heat exchangers.[66]  Oil-filled transformers undergo prolonged drying processes to ensure  that the transformer is completely free of water  vapor before the cooling oil is introduced. This helps prevent  electrical breakdown under load. Oil-filled transformers may be equipped  with Buchholz relays, which detect gas evolved  during internal arcing and rapidly de-energize the transformer to avert  catastrophic failure.[57]  Oil-filled transformers may fail, rupture, and burn, causing power  outages and losses. Installations of oil-filled transformers usually  includes fire protection measures such as walls, oil containment, and  fire-suppression sprinkler systems.
Polychlorinated biphenyls have  properties that once favored their use as a coolant,  though concerns over their environmental persistence led  to a widespread ban on their use.[68]  Today, non-toxic, stable silicone-based  oils, or fluorinated hydrocarbons may be used where the  expense of a fire-resistant liquid offsets additional building cost for a  transformer vault.[64][67]  Before 1977, even transformers that were nominally filled only with  mineral oils may also have been contaminated with polychlorinated  biphenyls at 10-20 ppm. Since mineral oil and PCB fluid  mix, maintenance equipment used for both PCB and oil-filled transformers  could carry over small amounts of PCB, contaminating oil-filled  transformers.[69]
Some "dry" transformers (containing no liquid) are enclosed in  sealed, pressurized tanks and cooled by nitrogen  or sulfur hexafluoride gas.[64]
Experimental power transformers in the 2 MVA range have been built  with superconducting windings which eliminates  the copper losses, but not the core steel loss. These are cooled by liquid nitrogen or helium
Insulation drying
Construction of oil-filled transformers requires that the insulation  covering the windings be thoroughly dried before the oil is introduced.  There are several different methods of drying. Common for all is that  they are carried out in vacuum environment. The vacuum makes it  difficult to transfer energy (heat) to the insulation. For this there  are several different methods. The traditional drying is done by  circulating hot air over the active part and cycle this with periods of  vacuum (hot-air vacuum drying, HAV). More common for larger transformers  is to use evaporated solvent which condenses on the colder active part.  The benefit is that the entire process can be carried out at lower  pressure and without influence of added oxygen. This process is commonly  called vapour-phase drying (VPD).
For distribution transformers, which are smaller and have a smaller  insulation weight, resistance heating can be used. This is a method  where current is injected in the windings to heat the insulation. The  benefit is that the heating can be controlled very well and it is energy  efficient. The method is called low-frequency heating (LFH) since the  current is injected at a much lower frequency than the nominal of the  grid, which is normally 50 or 60 Hz. A lower frequency reduces the  effect of the inductance in the transformer, so the voltage can be  reduced.
Terminals
Very small transformers will have wire leads connected directly to  the ends of the coils, and brought out to the base of the unit for  circuit connections. Larger transformers may have heavy bolted  terminals, bus bars or high-voltage insulated bushings made of polymers or porcelain.  A large bushing can be a complex structure since it must provide  careful control of the electric field gradient without  letting the transformer leak oil.[71]
Applications
A major application of transformers is to increase voltage before transmitting electrical energy  over long distances through wires. Wires have resistance and so  dissipate electrical energy at a rate proportional to the square of the  current through the wire. By transforming electrical power to a high-voltage (and  therefore low-current) form for transmission and back again afterward,  transformers enable economical transmission of power over long  distances. Consequently, transformers have shaped the electricity supply  industry, permitting generation to be located remotely from points  of demand.[72]  All but a tiny fraction of the world's electrical power has passed through a series of transformers  by the time it reaches the consumer.[43]
Transformers are also used extensively in electronic products to step down the supply voltage  to a level suitable for the low voltage circuits they contain. The  transformer also electrically isolates the end user from contact with  the supply voltage.
Signal  and audio  transformers are used to couple stages of amplifiers  and to match devices such as microphones  and record players to the input of  amplifiers. Audio transformers allowed telephone  circuits to carry on a two-way  conversation over a single pair of wires. A balun  transformer converts a signal that is referenced to ground to a signal  that has balanced voltages to ground, such as between  external cables  and internal circuits.
The principle of open-circuit (unloaded) transformer is widely used  for characterisation of soft magnetic materials, for example in the  internationally standardised Epstein  frame method
Toroidal inductors and transformers
From Wikipedia, the free encyclopedia
Toroidal  inductors and transformers are electronic components, typically  consisting of a circular ring-shaped magnetic  core of iron powder, ferrite, or other material around which wire is coiled  to make an inductor. Toroidal coils are used in a broad range  of applications, such as high-frequency coils and transformers.  Toroidal inductors can have higher Q factors  and higher inductance than similarly constructed solenoid  coils. This is due largely to the smaller number of turns required when  the core provides a closed magnetic path. The magnetic  flux in a high permeability toroid is largely confined to the core;  the confinement reduces the energy that can be absorbed by nearby  objects, so toroidal cores offer some self-shielding.
In the geometry of torus-shaped magnetic fields, the poloidal flux direction threads the  "donut hole" in the center of the torus, while the toroidal flux direction is parallel  the core of the torus.
Total B Field Confinement by Toroidal Inductors
In some circumstance, the current in the winding of a toroidal  inductor contributes only to the B field inside the windings and  makes no contribution to the magnetic B field outside of the  windings.
Sufficient conditions for total internal confinement of the B field
The absence of circumferential current [1]  (please refer to figure 1 of this section for definition of directions)  and the axially symmetric layout of the conductors and magnetic  materials [1][2][3]  are sufficient conditions for total internal confinement of the B  field. (Some authors prefer to use the H field). Because of the  symmetry, the lines of B flux must form circles of constant intensity  centered on the axis of symmetry. The only lines of B flux that encircle  any current are those that are inside the toroidal winding. Therefore,  from Ampere's circuital law, the intensity of the B field must be zero  outside the windings.[3]
Figure 3 of this section shows the most common toroidal winding. It  fails both requirements for total B field confinement. Looking out from  the axis, sometimes the winding is on the inside of the core and  sometimes it is on the outside of the core. It is not axially symmetric  in the near region. However, at points a distance of several times the  winding spacing, the toroid does look symmetric[4].  There is still the problem of the circumferential current. No matter  how many times the winding encircles the core and no matter how thin the  wire, this toroidal inductor will function as a one coil loop in the  plane of the toroid. This winding will also produce and be susceptible  to an E field in the plane of the inductor.
Figures 4-6 show different ways to neutralize the circumferential  current. Figure 4 is the simplest and has the advantage that the return  wire can be added after the inductor is bought or built.
] E Field in the Plane of the Toroid
There will be a distribution of potential along the winding. This can  lead to an E-Field in the plane of the toroid and also a  susceptibility to an E field in the plane of the toroid as shown  in figure 7. This can be mitigated by using a return winding as shown on  figure 8. With this winding, each place the winding crosses itself, the  two parts will be at equal and opposite polarity which substantially  reduces the E field generated in the plane.
Torroidal Inductor/Transformer and Magnetic Vector Potential
Main article: Magnetic potential
See Feynman chapter 14[5]  and 15[6]  for a general discussion of magnetic vector potential. See Feynman page  15-11 [7]  for a diagram of the magnetic vector potential around a long thin  solenoid which also exhibits total internal confinement of the B  field, at least in the infinite limit.
The A field is accurate when using the assumption bfA = 0. This would be true  under the following assumptions:
- 1. the Coulomb gauge is used
 - 2. the Lorenz gauge is used and  there is no distribution of charge, 

 - 3. the Lorenz gauge is used and zero frequency is assumed
 - 4. the Lorenz gauge is used and a  non-zero frequency that is low enough to neglect 
  is assumed. 
Number 4 will be presumed for the rest of this section and may be  referred to the "quasi-static condition".
Although the axially symmetric toroidal inductor with no  circumferential current totally confines the B field within the  windings, the A field (magnetic vector potential) is not  confined. Arrow #1 in the picture depicts the vector potential on the  axis of symmetry. Radial current sections a and b are equal distances  from the axis but pointed in opposite directions, so they will cancel.  Likewise segments c and d cancel. In fact all the radial current  segments cancel. The situation for axial currents is different. The  axial current on the outside of the toroid is pointed down and the axial  current on the inside of the toroid is pointed up. Each axial current  segment on the outside of the toroid can be matched with an equal but  oppositely directed segment on the inside of the toroid. The segments on  the inside are closer than the segments on the outside to the axis,  therefore there is a net upward component of the A field along  the axis of symmetry.
Representing the magnetic vector potential (A), magnetic flux (B), and  current density (j) fields around a toroidal inductor of circular cross  section. Thicker lines indicate field lines of higher average intensity.  Circles in cross section of the core represent B flux coming out of the  picture. Plus signs on the other cross section of the core represent B  flux going into the picture. Div A = 0 has been assumed.
Since the equations 
,  and 
  (assuming quasi-static conditions, i.e. 
  ) have the same form, then the lines and contours of A relate to  B like the lines and contours of B relate to j.  Thus, a depiction of the A field around a loop of B flux  (as would be produced in a toroidal inductor) is qualitatively the same  as the B field around a loop of current. The figure to the left  is an artist's depiction of the A field around a totoidal  inductor. The thicker lines indicate paths of higher average intensity  (shorter paths have higher intensity so that the path integral is the  same). The lines are just drawn to look good and impart general look of  the A field.
,  and 
  (assuming quasi-static conditions, i.e. 
  ) have the same form, then the lines and contours of A relate to  B like the lines and contours of B relate to j.  Thus, a depiction of the A field around a loop of B flux  (as would be produced in a toroidal inductor) is qualitatively the same  as the B field around a loop of current. The figure to the left  is an artist's depiction of the A field around a totoidal  inductor. The thicker lines indicate paths of higher average intensity  (shorter paths have higher intensity so that the path integral is the  same). The lines are just drawn to look good and impart general look of  the A field.[edit] Toroidal Transformer Action in the Presence of Total B field Confinement
The E and B fields can be computed from the A  and 
  (scalar electric potential) fields
  (scalar electric potential) fields
[8]  and  :
  [8]  and so even if the region outside the windings is devoid of B  field, it is filled with non-zero E field.
- The quantity 
  is responsible for the desirable magnetic field coupling between  primary and secondary while the quantity 
  is responsible for the undesirable electric field coupling between  primary and secondary. Transformer designers attempt to minimize the  electric field coupling. For the rest of this section, 
  will assumed to be zero unless otherwise specified. 
Stokes theorem applies[9],  so that the path integral of A is equal to the enclosed B  flux, just as the path integral B is equal to a constant times  the enclosed current
The path integral of E along the secondary winding gives the  secondary's induced EMF (Electro-Motive Force).
which says the EMF is equal to the time rate of change of the B flux  enclosed by the winding, which is the usual result.
[edit] Toroidal Transformer Poynting Vector Coupling from Primary to Secondary in the Presence of Total B field Confinement
Explanation of the Figure
This figure shows the half section of a toroidal transformer.  Quasi-static conditions are assumed, so the phase of each field is  everywhere the same. The transformer, its windings and all things are  distributed symmetrically about the axis of symmetry. The windings are  such that there is no circumferential current. The requirements are met  for full internal confinement of the B field due to the primary  current. The core and primary winding are represented by the gray-brown  torus. The primary winding is not shown, but the current in the winding  at the cross section surface is shown as gold (or orange) ellipses. The B  field caused by the primary current is entirely confined to the region  enclosed by the primary winding (i.e. the core). Blue dots on the left  hand cross section indicate that lines of B flux in the core come  out of the left hand cross section. On the other cross section, blue  plus signs indicate that the B flux enters there. The E  field sourced from the primary currents is shown as green ellipses. The  secondary winding is shown as a brown line coming directly down the axis  of symmetry. In normal practice, the two ends of the secondary are  connected together with a long wire that stays well away from the torus,  but to maintain the absolute axial symmetry, the entire apparatus is  envisioned as being inside a perfectly conductive sphere with the  secondary wire "grounded" to the inside of the sphere at each end. The  secondary is made of resistance wire, so there is no separate load. The E  field along the secondary causes current in the secondary (yellow  arrows) which causes a B field around the secondary (shown as  blue ellipses). This B field fills space, including inside the  transformer core, so in the end, there is continuous non-zero B  field from the primary to the secondary, if the secondary is not open  circuited. The cross product of the E field (sourced from primary  currents) and the B field (sourced from the secondary currents)  forms the Poynting vector which points from the primary toward the  secondary.







thanks sir for great info but iam confuse in transformer formula can u please explain more on easy steps like some more on inverter transformer please!
ReplyDelete